ACM3P Series
Three-Phase AC Ammeters
TECHNICAL NOTES, CONTINUED
5. Wiring: All power supply and load wiring must be rated for the volt-
ages and currents they will carry and must comply with any code or
application-mandated requirements pertaining to the user’s speci?c
installation.
6. Supply Fusing, and Grounding: Wires speci?ed in the Functional
Speci?cations section must be used for making connections to AC-
M3P series ammeters’ TB1 terminal block. No connection is required
for earth/chassis ground.
ACM3P series ammeters are not internally fused. Terminal block TB1
is to be used only for powering the ammeter's internal circuitry; it
must not be used to supply power to external loads. The supply wires
feeding these power meters must be fused with a 0.5A/250V time
delay/time lag fuse, in accordance with applicable regulatory codes.
Wire insulation must be stripped to within ±10% of the stated dimen-
sions, and wires should be inserted into TB1 such that their insulation
is not pinched by the screw terminal.
7. Current Transformer Phasing: Since the ACM3P only measures
amperes, transformer phasing is not required. ‘Phasing’ refers to the
direction of the current-carrying wire as it passes through the primary
hole of each of the three built-in current transformers.
PANEL
8. Connector Torque Ratings: It is important to tighten TB1’s screw-
terminals to their rated torque speci?cation of 3.6 pound-inches
(0.4Nm). Proper tightening will minimize connector losses and ensure
safe, reliable operation.
9. Isolation: Except for the 2-56 thread metallic mounting studs, all of
the ACM3P ammeter’s internal components (printed circuit board,
resistor, capacitors, current transformers L1, L2 and L3’s secondary
leads, etc.) are at the ac-mains potential connected to TB1. ACM3P
ammeters are designed to be powered from one ac power-source
only. Any other connection schemes could introduce signi?cant mea-
surement errors.
The three built-in current transformers have a dielectric breakdown
rating of 2kV minimum, allowing them to safely monitor 480V,
3-phase ac mains currents. This dielectric rating pertains only to the
insulated load-carrying wire as it passes through the built-in CT’s
primary hole. However, attention must still be paid to ensure adequate
wire-to-wire spacings, and wire-to-metallic surface spacings. Prop-
erly rated wiring and fusing must be used for all installations, as noted
in Technical Notes 5 and 6 above.
IMPORTANT: Even though ACM3P ac ammeters can be used in 480V
current monitoring applications, the ac supply connected to TB1 must
never exceed the maximum rating of 264V/47-63Hz.
PANEL INSTALLATION
All connections to ACM3P ammeters must be made after the unit is
ACM3P
SIDE VIEW
2-56 Hex Nuts (4 places)
Tighten each nut to 15 to 20
ozf-in (0.106 to 0.140 N-m).
L1
L2
L3
securely attached to the panel, and with all associated load and sup-
ply voltages de-energized (off), using extreme caution and observing
all safety measures applicable to the user’s installation.
Care should be exercised when passing conductors through the
ammeter’s built-in current transformers L1, L2, and L3. The installed
wire-positions should be such that minimal mechanical forces are
applied to the current transformers, TB1, or to the ACM3P ammeter
itself. In high-vibration environments, it is strongly recommended that
strain reliefs be used for all wiring.
Using Figure 1 as a guide, carefully insert the ACM3P assembly into
the panel opening. From the rear of the panel, install and then tighten
the four #2-56 hex nuts over the threaded studs. Tighten each nut to
15 to 20 ozf-in (0.106 to 0.140 N-m). Use only the factory-supplied
hardware as the use of substitute hardware could result in an unsafe
installation and/or adversely affect the reliability of the installation.
The recommended panel thickness range that can be used with the
supplied hardware is 0.040 inches (1.0mm) to 0.25 inches (6.4mm).
Panel thicknesses outside of this range may require additional user-
supplied hardware or modi?cations.
Figure 1. Panel Installation
www.murata-ps.com/support
MPM_ACM3P Series.A04 Page 3 of 6
相关PDF资料
AD5721R3 SWITCH ROLLER LEVER ASSMBLY
ADA3721R8 SWITCH ROLLER LEVER ASSMBLY
ADD1721R21 SWITCH ROLLER LEVER ASSMBLY
ADH3721R2 SWITCH ROLLER LEVER ASSMBLY
ADT3723R SWITCH ROLLER LEVER ASSMBLY
AE101SD1AQ04 SW TOGGLE SPDT 5AMP PCB
AE211MD1CB04 SWITCH TOGGLE SP3T 0.4VA T/H
AGX726 SWITCH INTERLOCK DOOR SAFETY 16A
相关代理商/技术参数
ACM4001A 制造商:AZDISPLAYS 制造商全称:AZ Displays 功能描述:ACM4001A SERIES LCD MODULE
ACM4002 制造商:AZDISPLAYS 制造商全称:AZ Displays 功能描述:SPECIFICATIONS FOR LIQUID CRYSTAL DISPLAY
ACM4002D 制造商:AZDISPLAYS 制造商全称:AZ Displays 功能描述:ACM4002D SERIES LCD MODULE
ACM4002E 制造商:ZETTLER 制造商全称:ZETTLER Electronics 功能描述:SPECIFICATIONS FOR LIQUID CRYSTAL DISPLAY
ACM4002E-ML-GBH-207 制造商:AZ Displays Inc 功能描述:
ACM4002E-RN-GBS 制造商:American Zettler Inc 功能描述:ACM Series 40 x 2 Reflective Grey STN COB Character LCD
ACM4002F 制造商:AZDISPLAYS 制造商全称:AZ Displays 功能描述:ACM4002F SERIES LCD MODULE
ACM4004C 制造商:AZDISPLAYS 制造商全称:AZ Displays 功能描述:MECHANICAL DATA